Overview
Smart-UPS On-Line provides high density, true double-conversion on-line power protection for servers, voice / data networks, medical labs, and light industrial applications. Capable of supporting loads from 1 to 20kVA in a rack/tower convertible form, the Smart-UPS On-Line is available from 2U to 12U. Recent family extensions at 15 and 20kVA enable support of power hungry blade servers or heavily loaded equipment racks. When business-critical systems require runtime in hours, not minutes, Smart-UPS On-Line can be configured with matching battery packs to comply with aggressive runtime demands. The included PowerChute management software provides unattended graceful shutdown of network operating systems. All models 5kVA and above include an integrated Network Management Card for remote management (optional on models below 5 kVA). The Smart-UPS On-Line family provides customers with a reliable source of uninterruptible power even in demanding power environments, including very wide input voltage window, extremely tight output voltage regulation, frequency regulation, internal bypass, and input power factor correction. |
Environmental Certification
Right View RoHS ENERGY STAR REACH |
Package Contents
APC Smart-UPS 2200VA SUA2200I Benutzerhandbuch. Vollbild Standard. Seite von 16 Los. Smart-UPS 2200/3000 VA 100/120/230 Vac Tower User Manual. Buy APC 2200VA Smart UPS with SmartConnect, SMT2200C Sinewave UPS Battery Backup, AVR, 120V, Line Interactive Uninterruptible Power Supply: Uninterruptible Power Supply (UPS) - Amazon.com FREE DELIVERY possible on eligible purchases.
- Smart-UPS SRT 2200VA 120V
- CD with software
- Documentation CD
- Installation guide
- Removable support feet
- USB cable
- Warranty card
General Information | |
Product Name | Smart-UPS SRT 2200VA 120V |
Manufacturer Part Number | SRT2200XLA |
Product Line | Smart-UPS |
Product Type | Dual Conversion Online UPS |
Technical Information | |
Receptacles | 6 x NEMA 5-20R 1 x NEMA L5-20R |
Battery Information | |
Typical Battery Recharge Time | 3 Hour |
Power Description | |
Load Capacity | 2200 VA/1800 W |
Input Voltage | 120 V AC |
Output Voltage | 120 V AC |
Physical Characteristics | |
Height | 17' |
Width | 3.3' |
Depth | 23' |
Form Factor | Rack/Tower |
Warranty | |
Limited Warranty | 3 Year |
Miscellaneous | |
Energy Star | Yes |
Environmentally Friendly | Yes |
Other Information | |
Product Family | Smart-UPS |
Load Capacity (VA) | 2200 VA |
Load Capacity (Watt) | 1800 W |
Smart-UPS®XL
Uninterruptible Power Supply
Rack-Mount 3U
SUA2200/3000 VA 120/230 Vac
SUA3000 VA 100/200 Vac
English
Introduction
Introduction
About this UPS
The APC Uninterruptible Power Supply (UPS) provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the batteries until utility power returns to safe levels or the batteries are fully discharged.
Accessories
This UPS is equipped with an accessory SmartSlot. Refer to the APC Web site, www.apc.com for available accessories.
If a standard accessory, such as a Network Management Card is installed on this UPS, refer to the accessory user manual or CD for installation and operation instructions.
Install accessories prior to connecting power to the UPS.
Unpack
Read the Safety Guide before installing the UPS.
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents:
• UPS | • Rail kit | ||
• Front bezel | • EPO connectors | ||
120 V Models Only: | 100/200 V Models Only: | 230 V Models Only: | |
UPS literature kit contents: | UPS literature kit contents: | UPS literature kit contents: | |
• Two rack-mount brackets | • Two rack-mount brackets | • Two rack-mount brackets | |
• Four cage nuts | • Four cage nuts | • Four cage nuts | |
• Eight flathead screws | • Eight flathead screws | • Eight flathead screws | |
• Product documentation | • Product documentation | • Product documentation | |
• Smart-UPS® User Manuals CD | • Serial communication cable | • Smart-UPS® User Manuals CD | |
• PowerChute® Business Edition CD | • Safety information | • PowerChute® Business Edition CD | |
• Serial and USB communication cable | • Warranty information | • Serial and USB communication cable | |
• Safety information | • Safety information | ||
• Warranty information | • Warranty information | ||
• Input power cord | |||
• Alternate input power cord | |||
(UK customers) | |||
• Utility connector plug | |||
• IEC jumper cables |
NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label is located on the chassis under the front bezel.
Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual | 3 |
Specifications
Specifications
Environmental
Temperature | This unit is intended for indoor | ||||||
Operating | 0° to 40°C (32° to 104°F) | use only. Select a location sturdy | |||||
Storage | -15° to 30°C (5° to 86°F) charge the UPS battery every six | enough to handle the weight. | |||||
months | Do not operate the UPS where | ||||||
30° to 45°C (86° to 113°F) charge the UPS battery every three | there is excessive dust or the | ||||||
months | temperature or humidity are | ||||||
outside the specified limits. | |||||||
Maximum | |||||||
Be sure the air vents on the | |||||||
Elevation | |||||||
UPS are not blocked. | |||||||
Operating | 3,000 m (10,000 ft) | ||||||
Environmental factors impact | |||||||
Storage | 15,240 m (50,000 ft) | ||||||
battery life. High temperatures, | |||||||
poor utility power, and frequent, | |||||||
Humidity | 0 to 95% relative humidity, non-condensing | ||||||
short duration discharges will | |||||||
shorten battery life. | |||||||
Physical | |||||||
Dimensions | 133 mm x 483 mm x 673 mm | ||||||
H/W/D | 5.2 in x 19 in x 27 in | ||||||
Weight | 73 kg (161 lbs) shipping weight | 63 kg (139 lbs) | |||||
63 kg (139 lbs) with battery module | |||||||
37 kg (82 lbs) without battery module | |||||||
Maximum Number of External Battery Packs Supported by the | 10 | ||||||
Smart-UPS XL | |||||||
Electrical | |||||||
100 V models | 120 V models | 200 V models | 230 V models | ||||
Output | |||||||
Output Frequency | 50/60 Hz +/– 3 Hz | ||||||
Nominal Output Voltage | 100 V | 120 V | 200 V | 230 V | |||
Input | |||||||
Input Frequency | 50/60 Hz +/– 3 Hz | ||||||
Nominal Input Voltage | 100 V | 120 V | 200 V | 230 V |
4 | Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual |
Installation
Installation
Your UPS model may vary in appearance from the examples depicted in this manual.
Apc Smart Ups 2200 Xl
The UPS and the battery modules are heavy. Remove the battery modules to lighten the UPS during installation.
Install the Rails in the Rack
This UPS is intended for installation in a 19” rack.
For details on rail installation refer to the instructions in the rail kit.
Install the UPS in the Rack and Connect the Battery Module
Install the UPS at or near the bottom of the rack.
$ |
& |
# |
Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual | 5 |
Installation
Rear Panels
2200/3000 VA 120 Vac
3000 VA 100 Vac
TVSS |
G ND |
Apc Smart Ups 2200 Powerchute Download Windows 7
Rear Panel Features
The UPS features a TVSS screw located on the rear panel for connecting the ground leads on | ||
transient voltage devices. | ||
The UPS is equipped with an external battery connector located on the rear panel of the unit. | ||
Where appropriate use an APC extension battery cable. For ordering details contact your dealer or | ||
APC through the Web site www.apc.com. | ||
120 V models only: The UPS is equipped with a Site Wiring Fault LED located on the rear panel of | ||
the unit. The LED will be illuminated if the UPS is plugged into an improperly wired utility power | ||
outlet, (see Troubleshooting in this manual). | ||
USB and Serial connectors are communication ports. | ||
Use only an APC approved cable to connect to the serial port. A standard serial interface cable | ||
USB | Serial | is incompatible with the UPS. |
Serial and USB ports cannot be used simultaneously. USB has priority over Serial. |
The UPS has a SmartSlot located on the rear panel for adding optional accessories to the unit.
100/120/200 V model circuit breaker and line cord connection.
230 V model circuit breaker and line cord connection.
The UPS is equipped with an emergency power off feature located on the rear panel of the unit.
6 | Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual |
Start-up and Operation
Connect equipment, external battery pack(s), and power to the UPS
Prior to connecting the grounding cable, ensure that the UPS is NOT connected to utility or battery power.
1.Connect equipment to the UPS.
2.Optional external battery packs provide extended runtime during power outages. This unit supports up to ten external battery packs. Refer to the APC Web site, www.apc.com for information. Refer to the user manual for the external battery pack for installation instructions.
Apc Smart Ups 2200 Model
3.Add optional accessories to the SmartSlot located on the rear panel.
4.Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
–230 V models: The utility power cord is supplied in the UPS literature kit. Prior to connecting the utility power, connect the ground lead (optional) to the chassis ground connection screw.
5.To use the UPS as a master on/off switch be sure all connected equipment is switched on.
Start-up and Operation
Start the UPS
1.Press the button on the front panel to start the UPS.
–When the UPS utilizes only an internal battery, the internal battery charges to 90% capacity during the first four hours of normal operation.
Do not expect full battery run capability during this initial charge period.
Apc Smart Ups 2200 Specifications
–The charge time for internal and external batteries will vary depending on the number of batteries connected to the UPS.

Apc Smart Ups 2200 Powerchute Download Software
Refer to the APC Web site, www.apc.com for battery runtimes.
2.For optimal computer system security, install PowerChute Smart-UPS monitoring software.